MEW R-1 — Section 15
Table 3.4B
عوامل القناة لحساب الملء (Table 3.4B)
Conduit factors for fill calculation
| نوع المسار | 16 مم | 20 مم | 25 مم | 32 مم | 38 مم | 50 مم |
|---|---|---|---|---|---|---|
| no_bend | 150 | 244 | 442 | 783 | 1092 | 1943 |
| one_bend | 120 | 196 | 358 | 643 | 883 | 1571 |
| two_bend | 86 | 141 | 260 | 474 | 646 | 1149 |
Use with Table 3.4A. Conduit factor must equal or exceed sum of cable factors.